Viessmann Fault code Viessmann
F8

Gas valve not closing properly

Breakdown: the boiler is stopped

On every Vitodens except the One Base (100-W, 200, 200-W, 222-F, 222-W, 300-W), the burner's gas valve closes too late or does not close: it is a fault that locks the burner out for safety, and the boiler only starts again after a reset. On a Vitodens One Base (200-W B2HF or B2KF, 222-F B2TF, 222-W B2LF), F.8 means something else: the hot water temperature sensor is short-circuited and the boiler no longer makes domestic hot water.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. On a Vitodens One Base (code F.8), do not reset the boiler: call us if the code stays on or comes back.
  3. Reset the boiler once only.
  4. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show F8?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code F8

The meaning depends on the boiler: find yours below.

F.8

Short circuit of the DHW temperature sensor

Blocking: it retries by itself Vitodens One Base
F8

Delayed closing of the fuel valve

Breakdown: the boiler is stopped Vitodens 100-W B1HA, Vitodens 100-W B1HC, Vitodens 100-W WB1A, Vitodens 100-W WB1B, Vitodens 100-W WB1C, Vitodens 200 WB2A, Vitodens 200-W B2HA, Vitodens 200-W WB2B, Vitodens 200-W WB2C, Vitodens 222-F B2SA, Vitodens 222-F B2TA, Vitodens 222-F FR2B, Vitodens 222-F FS2A, Vitodens 222-F FS2B, Vitodens 222-W B2LA, Vitodens 222-W WS2A, Vitodens 222-W WS2B, Vitodens 300-W B3HA, Vitodens 300-W B3HB
F8

The fuel valve or the modulation valve does not close

Breakdown: the boiler is stopped Vitodens 200-W B2HB, Vitodens 222-F B2SB, Vitodens 222-F B2TB, Vitodens 222-W B2LB

What our technician checks

  • The combined gas valve, replaced if needed
  • Both control paths of the gas valve (except Vitodens 200-W B2HB, 222-F B2TB and B2SB, 222-W B2LB)
  • Vitodens One Base: the hot water sensor connection (plug 5, terminals 3 and 4 on the HMU module), plugs, cables and corrosion
  • Vitodens One Base: the hot water sensor's resistance (NTC 10 kΩ), sensor replaced if needed

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.