Outdoor temperature sensor circuit broken
Blocking: it retries by itself
The outdoor temperature sensor, which measures the outside temperature to control the heating, gives no reading any more: its circuit is broken; on a Vitotronic 100 KC2B control, which runs at constant temperature, 18 rather means that a sensor was connected to the control by mistake. The boiler keeps heating: a Vitodens 100-W (B1HC, B1HA, WB1C, WB1B, WB1A) switches to constant-temperature operation, the Vitodens 200, 222-F, 222-W and 300-W and the floor-standing boilers with a Vitotronic 200 or 300 control heat as if it were 0 °C outside, the Vitotronic 100 KC2B runs normally, and our technician needs to check the sensor or the setting.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show 18?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 18
The meaning depends on the boiler: find yours below.
Open circuit of the outside temperature sensor
Open circuit of the outside sensor
A sensor has been inserted into the socket by mistake!
Open circuit Outside sensor
Open circuit outside sensor
What our technician checks
- The outdoor temperature sensor and its cable
- The sensor's resistance (NTC 10 kΩ), measured and compared with the curve; sensor or cable replaced depending on the result
- Vitotronic 100 KC2B: coding 25:0 in group 1 « General »