Combustion calibration interrupted
Breakdown: the boiler is stopped
On a Vitodens 200-W B2HB, 222-F B2TB or B2SB and 222-W B2LB, the boiler shut down on a process fault during the automatic calibration of its combustion; on a Vitodens 200-W WB2B or 222-W WS2A, it repeatedly could not get rid of enough heat during that calibration; on the other Vitodens 200-W, 222-F, 222-W and 300-W, the flame went out several times during the calibration. In every case the burner goes into fault: the boiler stops heating and only starts again after a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Check that the boiler's gas supply valve is open.
- On a Vitodens 200-W WB2B or 222-W WS2A: check that the thermostatic radiator valves are open, so that the boiler can pass on its heat.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show Eb?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code Eb
The meaning depends on the boiler: find yours below.
Malfunction, shutdown during calibration
Flame lost several times during calibration
Heat dissipation repeatedly too low during calibration
Shut-off malfunction during calibration
Repeated flame loss during calibration
Process error Shutdown during calibration
Repeated loss of flame during calibration
What our technician checks
- Condensate build-up in the system, to be cleared (remove the fan unit before the burner)
- The gas supply pressure and the inlet strainer of the combined gas valve
- The ionisation electrode: fouling and distance to the burner grid
- The gas type assignment
- The flue system, and any flue gas recirculation to be removed
- The internal extension H1 and the devices connected to it (plug 53/96, power interruption)
- The cable to the fan unit and the free running of the fan wheel
- Heat take-off during calibration (Vitodens 200-W WB2B and 222-W WS2A; on the WB2B, coding address 12:1)