Viessmann Fault code Viessmann
EA

Implausible flame signal during calibration

Breakdown: the boiler is stopped

During the automatic calibration of its combustion, the boiler measures an abnormal flame signal (ionisation current), too different from the one of the previous calibration: the cause is the electrode and its cable, flue gases getting back into the combustion air, dust or built-up condensate. The burner goes into fault: the boiler stops heating and only starts again after a reset.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.
  4. Keep paint, solvent and cleaning product fumes, and building dust, away from the boiler.

Does your boiler show EA?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code EA

The meaning depends on the boiler: find yours below.

EA

Ionisation current too low during calibration

Breakdown: the boiler is stopped Vitodens 200-W B2HB, Vitodens 222-F B2SB, Vitodens 222-F B2TB, Vitodens 222-W B2LB
EA

Ionisation current outside the valid range during calibration (deviation from the…

Breakdown: the boiler is stopped Vitodens 200-W B2HA, Vitodens 200-W WB2C, Vitodens 222-F B2SA, Vitodens 222-F B2TA, Vitodens 222-F FR2B, Vitodens 222-F FS2B, Vitodens 222-W B2LA, Vitodens 222-W WS2B, Vitodens 300-W B3HA, Vitodens 300-W B3HB
EA

Ionisation current outside the valid range during calibration

Breakdown: the boiler is stopped Vitodens 200-W WB2B, Vitodens 222-F FS2A, Vitodens 222-W WS2A

What our technician checks

  • The flue system, and any flue gas recirculation to be removed
  • The combustion air: dust (building work) or contamination in open-flue operation
  • The ionisation electrode, its connecting cable and the plug connections (loose contacts)
  • Condensate build-up in the system (remove the fan unit before the burner)
  • The boiler coding plug, to be replaced if the fault persists after several resets
  • The source of deposits on the electrodes in the boiler room and flue system (detergents, cleaning or personal care products)

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.