Flame signal too low during calibration
Breakdown: the boiler is stopped
During the automatic calibration of its combustion, shortly after the burner starts, the boiler measures a flame signal (ionisation current) that is too low: a fouled or badly placed electrode, a faulty cable or plug, or flue gases getting back into the combustion air. The burner goes into fault: the boiler stops heating and only starts again after a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
- Keep paint, solvent and cleaning product fumes, and building dust, away from the boiler.
Does your boiler show E7?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code E7
The meaning depends on the boiler: find yours below.
Ionisation current too low during calibration
What our technician checks
- The ionisation electrode: distance to the burner grid and fouling
- The electrode's connecting cable and the plug connections (loose contacts)
- The flue system, and any flue gas recirculation to be removed
- The source of deposits on the electrodes in the boiler room and flue system (detergents, cleaning or personal care products)
- After replacing the burner grid and the electrode: cleaning the fan unit, the gas-air duct and the Venturi extension