Remeha Fault code Remeha
E:02

Sensor short circuit or return too hot

Breakdown: the boiler is stopped

This code does not mean the same on every boiler: on a Calenta, Tzerra M or Quinta Pro (E:02), the flow temperature sensor is short-circuited, and on a Gas 210 Eco Pro it is the heat exchanger sensor; on an Avanta, Avanta Plus, Avanta Platinum Plus or Aquanta (E02), the water coming back from the system is hotter than the flow water, because of too little water, no circulation, air, a badly connected sensor or reversed wiring. In both cases the boiler locks out and stays off until the cause is removed and it is reset (on a Tzerra M, which has no display, the light on the button then flashes red).

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. On an Avanta or Aquanta: check the water pressure; below 1 bar, top up with water as the user manual explains.
  3. Reset the boiler once only.
  4. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show E:02?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code E:02

The meaning depends on the boiler: find yours below.

E02

Return temperature >

Breakdown: the boiler is stopped Avanta Platinum Plus, Avanta Plus
E02

Return temperature higher than the flow temperature

Breakdown: the boiler is stopped Aquanta, Avanta
E:02

Flow temperature sensor short-circuited

Breakdown: the boiler is stopped Calenta
E:02

Short circuit in the flow temperature sensor

Breakdown: the boiler is stopped Quinta Pro, Tzerra M
E:02

Short circuit in the heat exchanger temperature sensor

Breakdown: the boiler is stopped Gas 210 Eco Pro

The boilers that show this code

What our technician checks

  • The sensor wiring (E:02)
  • How the sensor is fitted and works, replaced if needed (E:02)
  • The system water pressure (E02)
  • The circulating pump: shaft freed with a screwdriver, wiring, replaced if it still does not run (E02)
  • Bleeding the air from the boiler and the system (E02)
  • The wiring between the sensors and the control unit (E02)
  • The flow and return sensors: 12 to 15 kΩ at 20 to 25 °C (E02)

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.