Safety parameters wrong or flow too hot
Breakdown: the boiler is stopped
This code does not mean the same on every boiler: on a Calenta, Tzerra M, Quinta Pro or Gas 210 Eco Pro (E:01), the control unit's safety parameters are incorrect, because of a bad connection or a faulty PSU board; on an Avanta, Avanta Plus, Avanta Platinum Plus or Aquanta (E01), the flow water has gone above the maximum temperature, because of too little water, no circulation, air in the system or a drifting sensor. In both cases the boiler locks out and stays off until the cause is removed and it is reset (on a Tzerra M, which has no display, the light on the button then flashes red).
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- On an Avanta or Aquanta: check the water pressure; below 1 bar, top up with water as the user manual explains.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show E:01?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code E:01
The meaning depends on the boiler: find yours below.
Flow temperature > Maximum operating temperature
Flow temperature >
The flow temperature is higher than the maximum set temperature.
The safety parameters are wrong
Safety parameters incorrect
The safety parameters are not in the right order
The boilers that show this code
What our technician checks
- The wiring of the control unit (E:01)
- The PSU board, replaced if faulty (Calenta, Tzerra M, Quinta Pro)
- The system water pressure, on the pressure gauge (E01)
- The circulating pump: shaft freed with a screwdriver, wiring, replaced if it still does not run (E01)
- Bleeding the air from the boiler and the system (E01)
- The flow and return sensors: 12 to 15 kΩ at 20 to 25 °C (E01)