External safety contact open
Breakdown: the boiler is stopped
A safety contact connected to the boiler is open: the external temperature limiter (TB 1, for example the one of an underfloor heating) has tripped, is faulty or locked, or the bridge on its terminals is missing; on a Cerapur ZWB-4 a failed condensate pump also gives this code. On a Cerapur ZWB-4 (D3 232) it is a blocking fault: the boiler starts again by itself once the contact closes; on the other models it stops and only starts again after a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Code D3 232 on a Cerapur ZWB-4: the boiler restarts by itself once the fault has cleared, do not reset it.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show d3?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code d3
The small number shown beside the code tells which.
Temperature limiter TB 1 faulty / The external temperature limiter has cut out /…
Jumper 161 on terminal strip ST 8 has not been recognised
Jumper 8-9 not detected
The temperature controller TB 1 has tripped / Temperature controller TB 1…
The boilers that show this code
What our technician checks
- The external temperature limiter TB 1 and its setting, unlocked if it is locked
- The temperature sensor and its cable (break, short circuit), replaced if needed
- The bridge on the external contact terminals (8-9, or bridge 161 on ST 8 for the ZWC-3), and the plug firmly seated
- The heating control setting (Cerapur ZWB-4)
- The condensate drain and the condensate pump, replaced if needed (Cerapur ZWB-4)