Viessmann Fault code Viessmann
84

Boiler's internal CO limit exceeded

Breakdown: the boiler is stopped

On the Vitodens 200-W B2HB, 222-F B2TB, 222-F B2SB and 222-W B2LB, the boiler has detected a carbon monoxide (CO) level above its internal limit. It is a fault: the boiler locks out its burner and only starts again after a reset, and our technician must check the whole flue gas path (leak, recirculation, water pocket, blockage).

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Smell of flue gas in the room? Switch the boiler off, air the room and close the doors to the living areas, then call us.
  3. Do not reset the boiler: call us.

Does your boiler show 84?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 84

The meaning depends on the boiler: find yours below.

84

Internal CO limit value of the appliance exceeded

Breakdown: the boiler is stopped Vitodens 200-W B2HB, Vitodens 222-W B2LB
84

CO limit value of the appliance exceeded

Breakdown: the boiler is stopped Vitodens 222-F B2SB, Vitodens 222-F B2TB

What our technician checks

  • The whole flue gas path: flue gas recirculation and leaks
  • A water pocket in the flue caused by too shallow a slope
  • A narrowing or a blockage in the flue
  • Servicing or repair of the flue system, if needed

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.