Daikin Fault code Daikin
8H

Water circuit overheating

Breakdown: the boiler is stopped

The heating water temperature has risen too high: 8H-00, the water leaving the indoor unit (above 65 °C on the older Altherma EKHB/EKHV, where 8H shows alone); 8H-01 and 8H-02, the mixed water circuit (on the Altherma 3 H HT and 3 R, 8H-01 also covers water that is too cold); 8H-03, overheating of the water circuit detected by the thermostat; 8H-08, the water circuit of the ECH2O models. It is an error code that an installer must reset after finding the cause, except 8H-01 and 8H-02 on a bizone Altherma low temperature (EHVZ): they clear by themselves and the screen refers to the bizone kit manual.

What you can do

  1. Write down the code shown and the heat pump model (on the rating plate).
  2. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show 8H?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 8H

The small number shown beside the code tells which.

8H

Outlet water temperature of indoor unit too high (>65°C)

Breakdown: the boiler is stopped Altherma LT EKHB/EKHV
8H
00

Abnormal increase outlet water temperature

Breakdown: the boiler is stopped Altherma 3 H, Altherma 3 H HT, Altherma 3 H MT, Altherma 3 M, Altherma 3 R, Altherma LT monobloc, Altherma LT split
8H
01

Overheating mixed water circuit

Breakdown: the boiler is stopped Altherma 3 H HT, Altherma 3 H MT, Altherma 3 M, Altherma 3 R, Altherma LT split
8H
02

Overheating mixed water circuit (thermostat)

Breakdown: the boiler is stopped Altherma 3 H HT, Altherma 3 H MT, Altherma 3 M, Altherma 3 R, Altherma LT split
8H
03

Overheating water circuit (thermostat)

Breakdown: the boiler is stopped Altherma 3 H, Altherma 3 H HT, Altherma 3 H MT, Altherma 3 M, Altherma 3 R, Altherma LT split
8H
08

Overheating water circuit

Breakdown: the boiler is stopped Altherma 3 H HT, Altherma 3 H MT, Altherma 3 R

What our technician checks

  • The electric backup heater contactor: not short-circuited
  • The outlet water thermistor, which must give a correct reading
  • The bizone kit, following its manual (8H-01, 8H-02 on a bizone Altherma low temperature)
  • The detailed troubleshooting of this code in the Daikin service manual