Water flow problem
Breakdown: the boiler is stopped
Not enough water is flowing through the heat pump (a closed valve, a dirty filter, air in the circuit, pressure too low or a pump fault; 7H alone on the older Altherma EKHB/EKHV). With 7H-01 it stops for a while and then restarts by itself; if the problem persists it stops and shows 7H-04 (hot water), 7H-05 (heating) or 7H-06 (cooling or defrost, with a risk of frost damage to the heat exchanger), and on an Altherma 3 also 7H-07 (pump unblocking in progress) or 7H-08 (pump fault): these codes stay on until an installer has found the cause and reset them.
What you can do
- Write down the code shown and the heat pump model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show 7H?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 7H
The small number shown beside the code tells which.
Flow failure (water flow too low or no water flow at all, minimum required water flow is…
Water flow problem
Water flow problem during domestic hot water production
Water flow problem during heating/sampling
Water flow problem during cooling/defrost
Water flow problem
Pump abnormality during operation (pump feedback)
What our technician checks
- The shut-off valves of the water circuit, fully open
- The water filter, cleaned if needed
- Air in the water circuit, bled out
- The water pressure on the gauge: above 1 bar, with cold water
- The expansion vessel and its isolating valve, open
- The pump speed and the resistance of the water circuit
- The circuit concerned by the sub-code: hot water (7H-04), heating (7H-05), plate heat exchanger and frost damage (7H-06)
- The circulation pump: rotor seized by limescale (7H-07) or a fault reported by the pump (7H-08)