Vaillant Fault code Vaillant
F.757

Compressor minimum run time missed too often

Breakdown: the boiler is stopped

On an aroTHERM pure, aroTHERM Split plus, aroTHERM pro or aroTHERM plus VWL ../8.1 (with or without iQconnect) heat pump, the compressor stopped several times before reaching its minimum run time, for example in a system without a buffer cylinder where the small heating water volume makes the temperature rise or fall very quickly at start-up. The heat pump goes into fault mode and stops until our technician has fixed the cause and restarted it.

What you can do

  1. Write down the code shown and the heat pump model (on the rating plate).
  2. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show F.757?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code F.757

The meaning depends on the boiler: find yours below.

F.757

The heat pump run time was shorter than the minimum run time of

Breakdown: the boiler is stopped aroTHERM Split plus VWL ../8.2 AS, aroTHERM pure VWL ../7.2 AS
F.757

During operation of the heat pump, the minimum run time of the

Breakdown: the boiler is stopped aroTHERM VWL ../7.1 A, ../8.1 A, aroTHERM VWL ../8.1 A Q

What our technician checks

  • The circulating heating water volume, increased if needed
  • The differential valve (bypass) (aroTHERM VWL ../7.1, ../8.1)
  • The circuit board, replaced if faulty (aroTHERM VWL ../8.1 A Q)

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.