Vaillant Fault code Vaillant
F.752

Compressor inverter fault

Breakdown: the boiler is stopped

On an aroTHERM, versoTHERM plus or recoCOMPACT exclusive heat pump, the frequency converter (inverter) that drives the compressor reports an internal fault or a compressor fault, for example a mains voltage outside the permitted range; on the aroTHERM VWL ../2 A, ../3 A a damaged inverter box, a blocked inverter box cooler or a wrongly set parameter can also be the cause. This is a fault: the heat pump no longer works normally (depending on the fault, it may keep running in emergency mode) and our technician has to find the cause.

What you can do

  1. Write down the code shown and the heat pump model (on the rating plate).
  2. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show F.752?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code F.752

The meaning depends on the boiler: find yours below.

F.752

Error: transformer

Breakdown: the boiler is stopped aroTHERM VWL ../2 A, ../3 A
F.752

Fault: inverter

Breakdown: the boiler is stopped aroTHERM VWL ../5 AS, aroTHERM plus VWL ../6 A, recoCOMPACT exclusive VWL ../5, versoTHERM plus VWL ../5
F.752

The inverter reports an internal fault or an undetermined compressor fault.

Breakdown: the boiler is stopped aroTHERM VWL ../7.1 A, ../8.1 A, aroTHERM VWL ../8.1 A Q, aroTHERM pure VWL ../7.2 AS

What our technician checks

  • The mains and compressor cables, and their plugs (clicked home)
  • The mains voltage (between 195 V and 253 V) and the phases
  • The inverter, replaced if necessary
  • The inverter box cooler (blocked)
  • The compressor parameter Max. power cut (aroTHERM VWL ../2 A, ../3 A)
  • A brief power cut to restart it, then customer service if the fault comes back (aroTHERM VWL ../8.1 A Q)