Compressor outlet temperature too low
Breakdown: the boiler is stopped
On a Vaillant aroTHERM VWL ../5 AS, aroTHERM plus VWL ../6 A, aroTHERM Split plus, aroTHERM VWL ../7.1 A and ../8.1 A, aroTHERM VWL ../8.1 A Q, versoTHERM plus or recoCOMPACT exclusive heat pump, the temperature at the compressor outlet is too low, lower than the condensing temperature: below 0 °C for more than 10 minutes, or below -10 °C, while the heat pump is working within its operating range. This is a refrigerant circuit fault for a technician to check; depending on the fault, the system may keep heating in emergency mode.
What you can do
- Write down the code shown and the heat pump model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show F.729?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code F.729
The meaning depends on the boiler: find yours below.
Compr. outlet temperature too low
The compressor outlet temperature is lower than the condensation temperature.
What our technician checks
- The high-pressure sensor
- On an aroTHERM VWL ../8.1 A Q: the compressor outlet sensor, if it differs by more than 4 K from the condensing temperature
- The operation of the electronic expansion valve
- The condenser outlet temperature sensor (subcooling)
- The 4-way valve, which must not stay in an intermediate position
- The refrigerant charge: overfilling, nitrogen or oxygen in the circuit
- On an aroTHERM VWL ../8.1 A Q: the circuit board, replaced if faulty
- For a fault in refrigerant circuit components: the manufacturer's service team