Elco Fault code Elco
118

Sensor check or water pressure too low

Breakdown: the boiler is stopped

On a Thision L Plus or Trigon L Plus, the sensor check of burner 1 or 2 (the figure shown after the code) has failed (display: Sensors Check), and the burner stays locked out until a reset. On a Thision S Plus, a Trigon S Plus or a Straton XL, this code means that the water pressure of the heating system is too low: the S Plus controller reports a fault, the Straton XL control panel a technical incident.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Thision S Plus, Trigon S Plus or Straton XL: read the water pressure on the gauge; if it is too low, top up the water through the filling tap, then check it again.
  3. Reset the boiler once only.
  4. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 118?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 118

The small number shown beside the code tells which.

118

Water pressure too low

Breakdown: the boiler is stopped Straton XL, Thision S Plus, Trigon S Plus
118
1

Sensors Check

Breakdown: the boiler is stopped Thision L Plus, Trigon L Plus
118
2

Sensors Check

Breakdown: the boiler is stopped Thision L Plus, Trigon L Plus

What our technician checks

  • Thision L Plus, Trigon L Plus: the flow sensors (T1, T1a) and the return sensor (T2) of the burner concerned and their wiring
  • Thision L Plus, Trigon L Plus: their resistances, measured with the boiler switched off and compared with the table (NTC 10k)
  • Thision L Plus, Trigon L Plus: the flow, flow 2 and return temperatures in the diagnostics (24.10 or 24.11)
  • Thision S Plus, Trigon S Plus: the water pressure sensor P1
  • Trigon S Plus: an operating pressure of at least 1.0 bar
  • Straton XL: the water pressure read by the controller (line 9005)
  • Thision S Plus, Trigon S Plus, Straton XL: leaks on the pipes and connections of the system
  • Thision S Plus, Trigon S Plus, Straton XL: the expansion vessel, the safety valve (3 bar on the S Plus) and the air vent

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.