Safety limiter or flow sensor fault
Breakdown: the boiler is stopped
On a Trigon XL, Trigon XXL, Thision S Plus or Trigon S Plus the safety temperature limiter has shut the boiler down because the water got too hot (on a Trigon XL also: return too hot, flow-return difference too large or temperature rising too fast), and the boiler is locked out. On a Thision L Plus or Trigon L Plus the flow sensor of the burner module shown after the code is open or short-circuited, and the boiler goes into fault.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 110?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 110
The small number shown beside the code tells which.
SLT lock-out
SLT lockout
Safety temperature limiter lockout
Flow Sensor Open Short Circuit
Flow Sensor Open Short Circuit
What our technician checks
- The water flow through the boiler (flow-return temperature difference)
- The safety limiter (SLT) and the TL limiter: tripped or open circuit
- The flow and return sensors (return hotter than flow)
- How fast the boiler temperature rises (TempGradMax)
- Thision L Plus or Trigon L Plus: the flow sensor (T1) of the module shown, measured with the boiler switched off against the resistance table (NTC 10 kΩ)