Elco Fault code Elco
117

Flow sensor 2 or water pressure too high

Breakdown: the boiler is stopped

On a Thision L Plus or Trigon L Plus, the second flow sensor of burner 1 or 2 (the figure shown after the code) is open or short-circuited, and the burner stays locked out until a reset. On a Thision S Plus, a Trigon S Plus or a Straton XL, this code means that the water pressure of the heating system is too high: the S Plus controller reports a fault, the Straton XL control panel a technical incident.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Thision S Plus, Trigon S Plus or Straton XL: read the water pressure on the gauge and give us the figure.
  3. Reset the boiler once only.
  4. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 117?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 117

The small number shown beside the code tells which.

117

Water pressure too high

Breakdown: the boiler is stopped Straton XL, Thision S Plus, Trigon S Plus
117
1

Flow2 Sensor Open Short Circuit

Breakdown: the boiler is stopped Thision L Plus, Trigon L Plus
117
2

Flow2 Sensor Open Short Circuit

Breakdown: the boiler is stopped Thision L Plus, Trigon L Plus

What our technician checks

  • Thision L Plus, Trigon L Plus: the second flow sensor (T1a) of the burner concerned and its wiring
  • Thision L Plus, Trigon L Plus: its resistance, measured with the boiler switched off and compared with the table (NTC 10k)
  • Thision L Plus, Trigon L Plus: the flow 2 temperature in the diagnostics (24.10.5 or 24.11.5)
  • Thision S Plus, Trigon S Plus: the water pressure sensor P1
  • Straton XL: the water pressure read by the controller (line 9005)
  • Thision S Plus, Trigon S Plus, Straton XL: the expansion vessel, the safety valve (3 bar on the S Plus) and the air vent