Buderus Fault code Buderus
A11

Controller: configuration, link or sensor fault

Blocking: it retries by itself

On a Logatherm or Bosch Compress heat pump (HMC300, HMC310 or HPC410 control), A11 reports a controller problem and the number next to it tells which one: system configuration not confirmed (1000), no communication over the EMS bus (1010), faulty outdoor temperature sensor (1037), invalid date or time (1038), no communication with the mixing valve module (3061 to 3064) or with the solar module (6004), or faulty room temperature sensor (3091 to 3094); for 3061 to 3064 and 3091 to 3094 the last digit gives the heating circuit, 1 to 4. The system keeps running as far as possible; with a faulty outdoor sensor the controller puts the heating into standby mode.

What you can do

  1. Write down the code shown and the heat pump model (on the rating plate).
  2. Number 1038: set the date and time, and avoid power cuts.
  3. HMC300 control, number 1010, 3061 to 3064 or 6004: check that the control unit sits properly in its wall bracket.
  4. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show A11?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

Buderus

Choose a real expert

Ecowatt is an approved Buderus System Partner: factory training in Germany, direct access to spare parts, one contact.

The variants of code A11

The small number shown beside the code tells which.

A11
1000

System configuration not confirmed

Blocking: it retries by itself HMC300, HMC310, HPC410
A11
1010

No communication via the EMS plus BUS connection

Blocking: it retries by itself HMC300, HMC310, HPC410
A11
1037

Outdoor temperature sensor faulty, heating standby mode active

Blocking: it retries by itself HMC300, HMC310, HPC410
A11
1038

Time/date invalid

Blocking: it retries by itself HMC300, HMC310, HPC410
A11
3061-3064

No communication with the mixing valve module

Blocking: it retries by itself HMC300, HMC310, HPC410
A11
3091-3094

Room temperature sensor faulty

Blocking: it retries by itself HMC300, HMC310, HPC410
A11
6004

No communication with the solar module

Blocking: it retries by itself HMC300, HMC310, HPC410

What our technician checks

  • The system configuration, completed then confirmed (1000)
  • The EMS bus wiring and cable, then the faulty bus device (1010)
  • The outdoor sensor: configuration, cable, corroded terminals and values checked against the table (1037)
  • The date and time setting, and long power cuts (1038)
  • The address set on the mixing valve or solar module, its bus cable (12 to 15 V DC) and the module itself (3061 to 3064, 6004)
  • The circuit's control type and its frost protection, or the controller or remote control to be replaced (3091 to 3094)

The same fault on other boilers

Recent boilers show alone the number older ones show beside the code.

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.