Skip to Content
+32 15 62 70 80 info@ecowatt.be Mon-Thu 07:30-17:00, Fri 07:30-13:30 Request a repair
Repair
Bosch Fault code Bosch
E9

A temperature limiter has tripped

Breakdown: the boiler is stopped

A safety device of the boiler has tripped: the flow or heat exchanger temperature limiter, which protects the boiler from water that is too hot, the flue gas limiter or, on a Condens 7000iW, the differential pressure switch; water pressure, air in the system, the circulating pump and the flue are the first things checked. It is a fault: the boiler stops and only starts again after a reset; on a Condens 7000iW (E9 224) it first waits for the fault to clear and only locks out if it lasts.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Check the water pressure on the gauge, with the boiler cold: at least 1 bar. Too low? Top up as your installer showed you.
  3. Reset the boiler once only.
  4. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show E9?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code E9

The small number shown beside the code tells which.

E9

The temperature limiter in the flow or the flue gas temperature limiter…

Breakdown: the boiler is stopped Condens 3000 W
E9
224

The thermostat or the flue gas temperature limiter or the differential pressure switch…

Breakdown: the boiler is stopped GC7000iW

The boilers that show this code

What our technician checks

  • The heat exchanger and flue gas temperature limiters and their cables (break, short circuit), replaced if needed
  • The heating system's operating pressure
  • Bleeding the air from the boiler (service function 2.2C on a Condens 7000iW)
  • The circulating pump: operation and power setting, replaced if needed
  • The fuse on the circuit board (Condens 3000 W)
  • The heat exchanger on the water side and, on a Condens 7000iW, its flow distributors
  • The flue, the tube and the differential pressure switch with its cable (Condens 7000iW)

The same fault on other boilers

Recent boilers show alone the number older ones show beside the code.

224

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.