Connection lost with module no. 8
Blocking: it retries by itself
The boiler no longer receives a correct setpoint from extension module WCM-EM no. 8 or remote control WCM-FS no. 8 on its communication bus (Thermo Condens WTC-A and WTC-OB); on a WTC-A driven by a 4-20 mA remote control (input N1), W88 also means that this signal is missing. It is an alarm: the boiler does not lock out and the code clears by itself once the connection is restored.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show W88?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code W88
The meaning depends on the boiler: find yours below.
The WCM-EM#8 or WCM-FS#8 no longer transmits a correct setpoint
Communication problem with EM#8 or WCM-FS#8
What our technician checks
- The addressing of the extension module or remote control
- The connecting cable and its connection
- The WCM-EM extension module or WCM-FS remote control, replaced if faulty
- The 4-20 mA setpoint signal and its connection (WTC-A)