Locked out: fast temperature rise or chamber overpressure
Breakdown: the boiler is stopped
Warning W19 kept coming back and the boiler has locked out: on a WTC-GW or WTC-GB B series boiler the flow water was heating up too fast, on a WTC-OB the combustion chamber pressure was too high (3 warnings in a row). It is a fault: do not reset the boiler, our technician has to find the cause, on the water side on the B series, in the heat exchanger and flue on the WTC-OB.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Do not reset the boiler: call us.
Does your boiler show F19?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code F19
The meaning depends on the boiler: find yours below.
Flow temp. (VPT) rises too quickly (gradient)
Combustion chamber pressure too high (see also W19)
What our technician checks
- The water flow through the boiler, increased if needed (B series)
- The pump's operation and settings (B series)
- Venting the water side (Automatic venting program, B series)
- The settings, adjusted with Weishaupt's help if needed (B series)
- The heat exchanger, cleaned if needed (WTC-OB)
- The flue and the condensate drain (WTC-OB)
- The combustion chamber pressure sensor, replaced if needed (WTC-OB)
- Flame stability and the mixing chamber pressure (WTC-OB)