Hot water or flue gas sensor short-circuited
Breakdown: the boiler is stopped
On a Vitopend 100-W WH1D in its heating-only version, the domestic hot water temperature sensor is short-circuited: the boiler no longer makes domestic hot water. On a Vitodens One Base (200-W B2HF or B2KF, 222-F B2TF, 222-W B2LF), F.50 means the flue gas temperature sensor is short-circuited: the burner locks out and the boiler only starts again after a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Vitodens One Base only: reset the boiler once only.
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show F50?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code F50
The meaning depends on the boiler: find yours below.
Short circuit of the flue gas temperature sensor
Short circuit of the DHW temperature sensor (single-function gas boiler)
What our technician checks
- Vitopend 100-W WH1D: the hot water temperature sensor
- Vitodens One Base: plug 15 on the BCU burner control unit: plug, wires, corrosion, cables
- Vitodens One Base: the flue gas sensor's resistance (NTC 10 kΩ) compared with the curve, faulty parts replaced
- Vitodens One Base: unlocking the appliance