Waiting time: compressor outlet too hot
Blocking: it retries by itself
On an aroTHERM VWL ..5/8.1 A Q or aroTHERM perform heat pump (VWZ AI /8 iQ module), the temperature at the compressor outlet is too high and the heat pump observes a waiting time. It is a reversible emergency-mode code: the heat pump runs in emergency mode and the code clears by itself.
What you can do
- Write down the code shown and the heat pump model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show L.303?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code L.303
The meaning depends on the boiler: find yours below.
Waiting time: compressor outlet temperature too high
What our technician checks
- The electronic expansion valve, checked with the sensor and actuator test
- The compressor inlet and outlet temperature sensors
- The condenser outlet temperature sensor (TT135)
- The refrigerant circuit filter: at most 4 K between before and after
- The refrigerant circuit for leaks, then refilling it
- The circuit board, replaced if faulty