Vaillant Fault code Vaillant
F.741

Heating return too cold

Breakdown: the boiler is stopped

On a Vaillant aroTHERM VWL ../5 AS, aroTHERM plus VWL ../6 A, versoTHERM plus or recoCOMPACT exclusive heat pump, the water returning from the heating dropped below 13 °C during defrosting: the compressor stays blocked while the code is shown, until the return rises above 20 °C again. On a flexoTHERM/flexoCOMPACT exclusive, the same code means the return is too cold for the compressor to start (below 5 °C when heating, below 10 °C when cooling).

What you can do

  1. Write down the code shown and the heat pump model (on the rating plate).
  2. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show F.741?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code F.741

The meaning depends on the boiler: find yours below.

F.741

Heating circuit: return temp. too low

Breakdown: the boiler is stopped aroTHERM VWL ../5 AS, aroTHERM plus VWL ../6 A, recoCOMPACT exclusive VWL ../5, versoTHERM plus VWL ../5
F.741

Building circuit: return temp. too low

Breakdown: the boiler is stopped flexoTHERM exclusive VWF ../4

What our technician checks

  • The system volume, at least the minimum volume, and a series return buffer tank if needed
  • The electric back-up heater, to be switched on to raise the return temperature
  • On a flexoTHERM, when heating: the operation of the 4-way valve

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.