Vaillant Fault code Vaillant
F.737

Condensing temperature too high

Breakdown: the boiler is stopped

On a Vaillant aroTHERM VWL ../5 AS, aroTHERM plus VWL ../6 A, aroTHERM Split plus, aroTHERM VWL ../7.1 A and ../8.1 A, aroTHERM VWL ../8.1 A Q, versoTHERM plus, recoCOMPACT exclusive or flexoTHERM/flexoCOMPACT exclusive heat pump, the refrigerant's condensing temperature is too high for the compressor to run: when heating, the heating water is too hot, for example because of outside heat input, too little water flow or an overfilled refrigerant circuit. This is a refrigerant circuit fault for a technician to check; depending on the fault, the system may keep heating in emergency mode.

What you can do

  1. Write down the code shown and the heat pump model (on the rating plate).
  2. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show F.737?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code F.737

The meaning depends on the boiler: find yours below.

F.737

Condensation temp. too high

Breakdown: the boiler is stopped aroTHERM VWL ../5 AS, aroTHERM plus VWL ../6 A, flexoTHERM exclusive VWF ../4, recoCOMPACT exclusive VWL ../5, versoTHERM plus VWL ../5
F.737

The condensation temperature of the refrigerant circuit is too high.

Breakdown: the boiler is stopped aroTHERM Split plus VWL ../8.2 AS, aroTHERM VWL ../7.1 A, ../8.1 A, aroTHERM VWL ../8.1 A Q

What our technician checks

  • Unwanted heat input, to be reduced or stopped
  • The back-up heater: does it heat while set to Off in the sensor and actuator test?
  • The electronic expansion valve: does it reach its end stop? (sensor and actuator test)
  • The compressor outlet sensor, sensor TT135 at the condenser outlet and the high-pressure sensor
  • The refrigerant quantity (overfilling)
  • The outdoor unit's service valves, which must be open
  • The air flow when cooling
  • The heating pump and the heating circuit flow

Related codes