High-pressure switch tripped
Breakdown: the boiler is stopped
On a Vaillant aroTHERM VWL ../5 AS, aroTHERM plus VWL ../6 A, aroTHERM Split plus, aroTHERM VWL ../7.1 A and ../8.1 A, aroTHERM VWL ../8.1 A Q, versoTHERM plus, recoCOMPACT exclusive or flexoTHERM/flexoCOMPACT exclusive heat pump, the refrigerant pressure has risen too high and the high-pressure switch has tripped (at 31.5, 41.5 or 46 bar depending on the model), for example because the condenser does not give off enough heat to the heating water. The heat pump stops; this is a refrigerant circuit fault, and a technician must reset the switch after finding the cause.
What you can do
- Write down the code shown and the heat pump model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show F.731?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
Choose a recognised installer
Ecowatt is a Vaillant installer: our group is on Vaillant's official list of installers.
The variants of code F.731
The meaning depends on the boiler: find yours below.
HP contact open
High-pressure switch tripped
HP switch open
What our technician checks
- Venting the heating circuit
- Water flow: room valves closed on underfloor heating
- The heating circuit strainers (clogging)
- Refrigerant flow: electronic expansion valve, jammed 4-way valve, clogged filter (manufacturer's service team)
- In cooling mode: fouling of the fan unit
- The high-pressure switch and the high-pressure sensor
- Resetting the high-pressure switch and the manual reset of the product
- On an aroTHERM VWL ../8.1 A Q: unwanted heat input, the back-up heater, the expansion valve and the heating pump