Skip to Content
+32 15 62 70 80 info@ecowatt.be Mon-Thu 07:30-17:00, Fri 07:30-13:30 Request a repair
Repair
Vaillant Fault code Vaillant
F.727

Refrigerant circuit high-pressure monitoring tripped

Breakdown: the boiler is stopped

On an aroTHERM pure or aroTHERM Split plus heat pump, the refrigerant circuit high-pressure monitoring has tripped; possible causes are too high a temperature at the compressor outlet, an electronic expansion valve that is not working properly, or too little refrigerant. The heat pump goes into fault mode and stops until our technician has fixed the cause and restarted it.

What you can do

  1. Write down the code shown and the heat pump model (on the rating plate).
  2. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show F.727?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code F.727

The meaning depends on the boiler: find yours below.

F.727

The high-pressure monitoring of the refrigerant circuit has tripped

Breakdown: the boiler is stopped aroTHERM Split plus VWL ../8.2 AS, aroTHERM pure VWL ../7.2 AS

What our technician checks

  • The compressor inlet and outlet temperature sensors
  • The condenser outlet temperature sensor (TT135)
  • The electronic expansion valve, tested with the sensor/actuator test, replaced if needed
  • The refrigerant charge and the tightness of the refrigerant circuit
  • That the outdoor unit service valves are open
  • Heat dissipation: room valves and shut-off valves open, fan coils running in heating mode (aroTHERM Split plus)

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.