Flow temperature too high
Breakdown: the boiler is stopped
On a GMR 1000 Condens, the water leaving the boiler (flow) has gone above the maximum operating temperature, for example because the water pressure is too low, the water is not circulating, there is too much air or a sensor reads wrongly. The boiler stops and the code flashes on the display; it only restarts after a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Check the water pressure on the boiler's pressure gauge: below 1 bar, top up the water as your installer showed you.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show E01?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code E01
The meaning depends on the boiler: find yours below.
Flow temperature > maximum operating temperature
The boilers that show this code
What our technician checks
- The system water pressure (pressure gauge)
- The boiler circulation pump: shaft freed with a screwdriver, wiring, replaced if it does not run
- Bleeding the boiler, with the pump off
- The flow and return sensors: operation and resistance with a multimeter (12 to 15 kOhm at 20 to 25 °C)