Air pressure switch open (APS)
Breakdown: the boiler is stopped
On a Thision L Plus or Trigon L Plus, the air pressure switch (APS), which watches the combustion air, has opened for burner 1 or 2 (the figure shown after the code) and has put the boiler into fault. As a precaution we treat this code as a possible flue problem: the boiler must stay off until our technician has been.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Do not reset the boiler: call us.
Does your boiler show 603?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 603
The small number shown beside the code tells which.
APS Open
APS Open
What our technician checks
- The differential air pressure switch: switching pressure between 5.0 and 6.5 mbar
- The pressure switch hoses: condition, tightness and clean connection points
- The combustion air intake
- The tightness of the flue
- The non-return flap under the burner cassette: full closing and free movement
- The siphon, its dirt trap and the condensate drain