Flow check failed three times
Breakdown: the boiler is stopped
On a Thision L Plus or Trigon L Plus, flow check 4 (or 1 or 3), which checks the water flow, has failed three times on burner 1 or 2 (the figure shown after the code), after the warnings 1P3, 1P1 or 1P2. This is a locking fault: the burner stays off until a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 106?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 106
The small number shown beside the code tells which.
Flow Check 4 (or 1 or 3) Three Times
Flow Check 4 (or 1 or 3) Three Times
What our technician checks
- The circulating pump: operation, noise, damage and leaks
- The flow rate and modulation of the pump of the burner concerned (diagnostics 24.10 or 24.11)
- The system pressure (plausibility check)
- The automatic air vent and the venting of the system
- The water connections: damage, corrosion and leaks
- The flow and return temperatures of the burner concerned (diagnostics 24.10 or 24.11)
- The flow and return sensors, measured with the boiler switched off and compared with the resistance table (NTC 10k)