Elco Fault code Elco
506

Weak flame at high fan speed

Breakdown: the boiler is stopped

On a Thision L Plus or Trigon L Plus, the burner module shown after the code (1 or 2) detects a weak flame while its fan, which sets the output, is running fast. It is a flame fault: the module goes into fault and waits for a reset, which our technician does once the cause is found.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show 506?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 506

The small number shown beside the code tells which.

506
1

Flame Low Fan RPM High

Breakdown: the boiler is stopped Thision L Plus, Trigon L Plus
506
2

Flame Low Fan RPM High

Breakdown: the boiler is stopped Thision L Plus, Trigon L Plus

What our technician checks

  • The flame and, if it is not stable, the settings and the burner
  • The ignition and ionisation electrode, and the ionisation current
  • The combustion: O2/CO2 measurement
  • The combustion air intake
  • The fan unit and the burner cassette, to be cleaned
  • The static and dynamic gas pressure