Flame lost repeatedly
Breakdown: the boiler is stopped
On a Thision L Plus or Trigon L Plus, the flame of burner 1 or 2 (the figure shown after the code) has lifted off and been lost several times while running. This is a locking fault: the burner stays off until a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 504?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 504
The small number shown beside the code tells which.
Flame lift (3 attempts)
Flame lift (3 attempts)
What our technician checks
- The flame stability, the settings and the burner
- The O2/CO2 setting and the ionisation current
- The static and dynamic gas pressure
- The detection electrode: ionisation current of at least 4 μA at full load
- The burner cassette: wear, dirt and breakage
- The combustion air intake
- The tightness of the flue