Elco Fault code Elco
501

No flame detected at ignition

Breakdown: the boiler is stopped

On a Thision L Plus or Trigon L Plus, burner 1 or 2 (the figure shown after the code) has tried several times to light without any flame being detected. This is a locking fault: the burner stays off until a reset.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 501?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 501

The small number shown beside the code tells which.

501
1

No Flame detection (3 attempts)

Breakdown: the boiler is stopped Thision L Plus, Trigon L Plus
501
2

No Flame detection (3 attempts)

Breakdown: the boiler is stopped Thision L Plus, Trigon L Plus

What our technician checks

  • The ignition electrode: condition, wear, resistance of 100 Ω at most
  • The detection electrode: ionisation current of at least 4 μA at full load
  • The electrode cable and its fuse, if the electrode is damaged
  • The static and dynamic gas pressure
  • The gas valve and the venturi: damage, corrosion and operation
  • The O2/CO2 setting and the ionisation current
  • The combustion air intake
  • The siphon, its dirt trap and the condensate drain

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.