Skip to Content
+32 15 62 70 80 info@ecowatt.be Mon-Thu 07:30-17:00, Fri 07:30-13:30 Request a repair
Repair
Elco Fault code Elco
451

BMS current configuration error

Breakdown: the boiler is stopped

On a Thision L Plus or Trigon L Plus, the boiler can take its heat demand from a building management system (BMS), and the settings of this control by current signal (mA) do not match. This is a locking fault: it stays on the display until a reset, and if it comes back our technician has to find the cause.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 451?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 451

The meaning depends on the boiler: find yours below.

451

Bms Current Configuration Error

Breakdown: the boiler is stopped Thision L Plus, Trigon L Plus

What our technician checks

  • The BMS control mode selected (parameter 42.0.0)
  • The current control thresholds (parameters 42.1.4 to 42.1.7)
  • The current received at the BMS input (diagnostics 42.2.4)
  • The BMS status in the diagnostics (42.2.0, configuration error)

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.