BMS current configuration error
Breakdown: the boiler is stopped
On a Thision L Plus or Trigon L Plus, the boiler can take its heat demand from a building management system (BMS), and the settings of this control by current signal (mA) do not match. This is a locking fault: it stays on the display until a reset, and if it comes back our technician has to find the cause.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 451?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 451
The meaning depends on the boiler: find yours below.
Bms Current Configuration Error
What our technician checks
- The BMS control mode selected (parameter 42.0.0)
- The current control thresholds (parameters 42.1.4 to 42.1.7)
- The current received at the BMS input (diagnostics 42.2.4)
- The BMS status in the diagnostics (42.2.0, configuration error)