Elco Fault code Elco
40

Return temperature sensor fault

Breakdown: the boiler is stopped

The sensor that measures the temperature of the water coming back from the system to the boiler (return sensor) is short-circuited, open or faulty. The boiler goes to safety shutdown and stops heating; on a Trigon XL or Trigon XXL the fault clears by itself and the boiler restarts as soon as the sensor is plugged back in and working.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 40?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 40

The meaning depends on the boiler: find yours below.

40

Return temperature 1 sensor fault

Breakdown: the boiler is stopped Trigon XL
40

Return temperature 1 sensor error

Breakdown: the boiler is stopped Trigon XXL
40

Return temperature sensor 1 fault

Breakdown: the boiler is stopped Thision S Plus, Trigon S Plus

What our technician checks

  • The return sensor (B7) and its plug: short or open circuit
  • The sensor resistance, boiler switched off (NTC 10 kΩ on a Trigon XXL)
  • The test after repair: plug off gives code 40, plug back on and the boiler restarts