Outdoor temperature sensor fault
Breakdown: the boiler is stopped
The controller is not getting a valid reading from the outdoor temperature sensor: sensor disconnected, broken, faulty or reading impossible. On a Trigon XL, Trigon XXL, Thision S Plus or Trigon S Plus the manual lists this code among the lockouts, to be reset once the cause is removed; on a Straton XL the controller reports it and the manual does not speak of a lockout.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 10?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 10
The meaning depends on the boiler: find yours below.
Outside sensor fault
Outside temperature sensor error
Outside temperature sensor fault
Outside temperature sensor
What our technician checks
- The outdoor sensor (B9), its cable and its connection
- The sensor resistance (NTC 1 kΩ), measured with the boiler switched off, as close to the sensor as possible
- With no outdoor sensor connected: installation frost protection (parameter 6120) set to off and saved with parameter 6200
- With a wireless outdoor sensor: its batteries