Sensor input BX2 not working
Breakdown: the boiler is stopped
The controller reports that its sensor input BX2 is not working (on a Trigon XL this input takes the header or heat exchanger flow sensor, on a Trigon XXL the header temperature sensor). On a Trigon XL, Trigon XXL, Thision S Plus or Trigon S Plus the boiler goes into safety lockout and the cause must be removed before it is reset; on a Straton XL the code shows as a technical fault.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- On a Trigon XL, Trigon XXL, Thision S Plus or Trigon S Plus, the boiler has gone into safety lockout.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
- On a Straton XL this code is a technical fault: do not reset the boiler.
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show 331?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 331
The meaning depends on the boiler: find yours below.
Sensor input BX2 no function
Sensor BX2 no function
BX2 no function
What our technician checks
- The sensor on input BX2, its cable and its connection (terminals 104 and 105 on a Trigon XL or XXL)
- The function set for input BX2 (programming line 5931 on a Thision S Plus, Trigon S Plus or Straton XL)
- The sensor's resistance, measured as close to the sensor as possible and compared with the maker's values