Elco Fault code Elco
128

Flame lost during operation

Breakdown: the boiler is stopped

The burner was lit and the flame went out during operation. The boiler tries to restart, then goes to safety shutdown (on a Trigon XL, when the repeat counter is exceeded) and stops heating until it is reset.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 128?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 128

The meaning depends on the boiler: find yours below.

128

Loss of flame in operation

Breakdown: the boiler is stopped Trigon XL
128

Loss of flame during operation

Breakdown: the boiler is stopped Trigon S Plus, Trigon XXL
128

Flame failure during operations

Breakdown: the boiler is stopped Thision S Plus

What our technician checks

  • The ionisation electrode, its cable and its connection
  • The ionisation current, measured with a multimeter set to µA and compared with the model's minimum
  • The gas pressure at the boiler
  • The combustion values at full and minimum load
  • The ignition and ionisation electrodes, to be replaced at the service

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.