Elco Fault code Elco
332

Sensor input BX3 not working

Breakdown: the boiler is stopped

The controller reports that its sensor input BX3 is not working: on a Trigon XL the cause given is a wrongly programmed flue gas sensor, and on a Thision S Plus or Trigon S Plus this input takes the flue gas temperature sensor as delivered. The boiler goes into safety lockout and the cause must be removed before it runs again: that reset is for our technician.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Do not reset the boiler: call us.

Does your boiler show 332?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 332

The meaning depends on the boiler: find yours below.

332

Sensor input BX3 no function

Breakdown: the boiler is stopped Trigon XL
332

Sensor BX3 no function

Breakdown: the boiler is stopped Thision S Plus, Trigon S Plus, Trigon XXL

What our technician checks

  • The programming of the flue gas sensor (Trigon XL)
  • The function set for input BX3 (line 5932, set to the B8 flue gas sensor as delivered on a Thision S Plus or Trigon S Plus)
  • The flue gas sensor and its cable (open circuit or short circuit)
  • The sensor's resistance, measured as close to the sensor as possible and compared with the maker's values