Sensor input BX3 not working
Breakdown: the boiler is stopped
The controller reports that its sensor input BX3 is not working: on a Trigon XL the cause given is a wrongly programmed flue gas sensor, and on a Thision S Plus or Trigon S Plus this input takes the flue gas temperature sensor as delivered. The boiler goes into safety lockout and the cause must be removed before it runs again: that reset is for our technician.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Do not reset the boiler: call us.
Does your boiler show 332?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 332
The meaning depends on the boiler: find yours below.
Sensor input BX3 no function
Sensor BX3 no function
What our technician checks
- The programming of the flue gas sensor (Trigon XL)
- The function set for input BX3 (line 5932, set to the B8 flue gas sensor as delivered on a Thision S Plus or Trigon S Plus)
- The flue gas sensor and its cable (open circuit or short circuit)
- The sensor's resistance, measured as close to the sensor as possible and compared with the maker's values