Flue gas temperature sensor fault
Breakdown: the boiler is stopped
The sensor that monitors the flue gas temperature is open, short-circuited or faulty: the boiler can no longer check its flue gases and goes to safety shutdown. Do not reset it yourself: on a Trigon XL or Trigon XXL it restarts by itself as soon as the sensor works again.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Do not reset the boiler: call us.
Does your boiler show 28?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 28
The meaning depends on the boiler: find yours below.
Flue gas temperature sensor fault
Flue gas temperature sensor error
Flue gas / exhaust temperature sensor fault
What our technician checks
- The flue gas sensor and its plug: open or short circuit
- The sensor resistance, boiler switched off (NTC 10 kΩ on a Trigon XXL)
- The test after repair: plug off gives code 28, plug back on and the boiler restarts