Elco Fault code Elco
1P2

Flow check 3 failed

Blocking: it retries by itself

On a Thision L Plus or Trigon L Plus, flow check 3 (display: Flow Check 3, a check of the water flow) has failed on burner 1 or 2 (the figure shown after the code). This is a warning: the boiler tries again by itself, but if flow checks 3, 1 or 4 fail three times, it locks the burner out (code 105).

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show 1P2?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 1P2

The small number shown beside the code tells which.

1P2
1

Flow Check 3

Blocking: it retries by itself Thision L Plus, Trigon L Plus
1P2
2

Flow Check 3

Blocking: it retries by itself Thision L Plus, Trigon L Plus

What our technician checks

  • The circulating pump: operation, noise, damage and leaks
  • The flow rate and modulation of the pump of the burner concerned (diagnostics 24.10 or 24.11)
  • The system pressure (plausibility check)
  • The automatic air vent and the venting of the system
  • The water connections: damage, corrosion and leaks
  • The flow and return temperatures of the burner concerned (diagnostics 24.10 or 24.11)
  • The flow and return sensors, measured with the boiler switched off and compared with the resistance table (NTC 10k)