Buderus Fault code Buderus
H01

Heat pump alarm

Breakdown: the boiler is stopped

On a Logatherm or Bosch Compress heat pump (HMC300, HMC310 or HPC410 control), H01 reports a heat pump fault, most often an alarm, and the number next to it tells which one: air in the circuit (5594) or hot water sensor TW1 fault (5239) on all three controls; on the HMC300, flow limited by a dirty filter (5252, 5253, 5451, 5455), a high or low pressure sensor alarm (5283, 5292, 5293, 5501), defrost failed (5463), moisture on the flow pipes (5295), frost protection active (5375, 5377) or thermal disinfection not carried out (5284); on the HMC310 and HPC410, a fault of the compressor or its power supply (5803 to 5817), of the 4-way valve (5821) or an unknown outdoor unit code (5828). On the HMC310 and HPC410 the compressor faults lock the outdoor unit; on the HMC300 the system keeps running as far as possible, and with frost protection the pumps and the heat pump are even forced on.

What you can do

  1. Write down the code shown and the heat pump model (on the rating plate).
  2. HMC300 control, number 5252, 5253, 5451 or 5455 (and 5292 or 5293 on a Logatherm WSW196i-12 ground source heat pump): the particle filter may be dirty; clean it.
  3. HMC300 control on an air-to-water heat pump, number 5283, 5292, 5293, 5463 or 5501: clean the outdoor unit, especially the evaporator and the fan.
  4. Number 5295 (HMC300): moisture has formed on the pipes; wait until it has dried, then confirm the alarm by pressing the rotary knob.
  5. Number 5375 or 5377 (HMC300): frost protection is active; do not switch the heating off during the heating season.
  6. Number 5284 (HMC300): avoid drawing hot water continuously during the thermal disinfection, or change the time of the thermal disinfection.
  7. Reset the heat pump once only.
  8. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show H01?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

Buderus

Choose a real expert

Ecowatt is an approved Buderus System Partner: factory training in Germany, direct access to spare parts, one contact.

The variants of code H01

The small number shown beside the code tells which.

H01
5239

DHW sensor TW1 fault

Breakdown: the boiler is stopped HMC300, HMC310, HPC410
H01
5252

Z1 Volume flow between outdoor and indoor units restricted

Blocking: it retries by itself HMC300
H01
5253

Z2 Volume flow between outdoor and indoor units restricted

Blocking: it retries by itself HMC300
H01
5283

Z2 High-pressure sensor

Breakdown: the boiler is stopped HMC300
H01
5284

Last thermal disinfection could not be carried out

Blocking: it retries by itself HMC300
H01
5292

Z1 High-pressure sensor

Breakdown: the boiler is stopped HMC300
H01
5293

Z1 Low-pressure sensor

Breakdown: the boiler is stopped HMC300
H01
5295

Condensation sensor

Breakdown: the boiler is stopped HMC300
H01
5375

Z1 Frost protection activated

Breakdown: the boiler is stopped HMC300
H01
5377

Z2 Frost protection activated

Breakdown: the boiler is stopped HMC300
H01
5451

Z1 Flow rate too low during defrost

Breakdown: the boiler is stopped HMC300
H01
5455

Z2 Flow rate too low during defrost

Breakdown: the boiler is stopped HMC300
H01
5463

Z1 Defrost failed

Breakdown: the boiler is stopped HMC300
H01
5501

Z2 Low-pressure sensor

Breakdown: the boiler is stopped HMC300
H01
5594

Air in the system

Breakdown: the boiler is stopped HMC300, HMC310, HPC410
H01
5803

No power supply at compressor

Breakdown: the boiler is stopped HMC310, HPC410
H01
5805

Current sensor fault

Breakdown: the boiler is stopped HMC310, HPC410
H01
5807

IPM driver pin fault

Breakdown: the boiler is stopped HMC310, HPC410
H01
5809

AC input zero cross error

Breakdown: the boiler is stopped HMC310, HPC410
H01
5811

Compressor current sensor fault

Breakdown: the boiler is stopped HMC310, HPC410
H01
5813

Compressor driver pin fault

Breakdown: the boiler is stopped HMC310, HPC410
H01
5815

PFC current sensor fault

Breakdown: the boiler is stopped HMC310, HPC410
H01
5817

PFC over current fault

Breakdown: the boiler is stopped HMC310, HPC410
H01
5821

Low evaporating temperature in heating (faulty reverse valve)

Blocking: it retries by itself HMC310, HPC410
H01
5828

Unspecified outdoor unit fault

Breakdown: the boiler is stopped HMC310, HPC410

What our technician checks

  • Valves restricting the flow, the primary circulation pump and venting the unit (5594)
  • Hot water sensor TW1 and its cable, measured against the sensor table, then the installer circuit board (5239)
  • The particle filter and the flow between indoor and outdoor units (HMC300)
  • Dirt on the outdoor unit, the evaporator and the fan (HMC300)
  • The minimum permitted flow temperature, to be raised in the service menu (5295)
  • The compressor wiring, connections and internal resistances, the high pressure switch connection and the air inlet of the outdoor coil (5803 to 5807)
  • The input voltage between phases and neutral, the power cables and the compressor drive (5809 to 5817)
  • The 4-way valve, the refrigerant charge and the ICT sensor (5821), and the code read on the outdoor unit controller display (5828)

The same fault on other boilers

Recent boilers show alone the number older ones show beside the code.

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.