Buderus Fault code Buderus
A51

Solar collector or cylinder sensor faulty

Blocking: it retries by itself

On a Logatherm or Bosch Compress heat pump (HMC300, HMC310 or HPC410 control) connected to a solar system, a solar sensor is faulty or badly connected, and the number next to it tells which one: the solar collector temperature sensor (6021) or the bottom sensor of cylinder 1 (6022, with standby mode). The system keeps running as far as possible.

What you can do

  1. Write down the code shown and the heat pump model (on the rating plate).
  2. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show A51?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

Buderus

Choose a real expert

Ecowatt is an approved Buderus System Partner: factory training in Germany, direct access to spare parts, one contact.

The variants of code A51

The small number shown beside the code tells which.

A51
6021

Collector temperature sensor faulty

Blocking: it retries by itself HMC300, HMC310, HPC410
A51
6022

Cylinder 1 bottom temperature sensor, standby mode active

Blocking: it retries by itself HMC300, HMC310, HPC410

What our technician checks

  • The solar configuration, which needs this sensor
  • The cable between the solar module and the sensor, and its connection on the module
  • The sensor, checked against the table, replaced if the values differ
  • The voltage at the sensor terminals on the solar module, and the module if it does not match

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.