Remote control signal on N1 too low
Breakdown: the boiler is stopped
On a remotely controlled WTC-GW or WTC-GB B series boiler, the 0 to 10 V signal that an external controller sends to input N1 to set the flow temperature has been too low for about 15 minutes. This is a fault: the boiler locks out if it can no longer run safely, and the display then offers to unlock it.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show F80?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code F80
The meaning depends on the boiler: find yours below.
Remote control signal (N1) too low
What our technician checks
- The 0 to 10 V signal on input N1, connected with the right polarity
- The voltage limits set for burner shutdown and fault reporting