Weishaupt Fault code Weishaupt
F12

Flow water above 95 °C

Breakdown: the boiler is stopped

On a WTC-OB, the water leaving the boiler has repeatedly gone above 95 °C: after 12 W12 alarms, the boiler locks out with F12 and does not restart by itself. The causes lie in the water circulation through the boiler: flow too low, air, fouled or scaled heat exchanger.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show F12?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code F12

The meaning depends on the boiler: find yours below.

F12

Temperature at flow sensor > 95 °C

Breakdown: the boiler is stopped WTC-OB (WCM-OB)

What our technician checks

  • The water flow through the boiler, increased if too low
  • Venting the air on the water side
  • The heat exchanger on the water side: fouling or scale