Circuit 3 flow sensor short-circuited
Blocking: it retries by itself
On a Vitodens One Base (200-W B2HF or B2KF, 222-F B2TF, 222-W B2LF, 242-F), the flow temperature sensor of heating circuit 3 (mixing valve circuit) is short-circuited. The boiler keeps running, but that circuit's mixing valve closes while its pump keeps running: the circuit no longer heats properly and our technician needs to check the sensor.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show F.547?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code F.547
The meaning depends on the boiler: find yours below.
Short circuit of flow temperature sensor HC 3
What our technician checks
- The setting of rotary switch S1 on the ADIO electronics module (mixing valve extension)
- The flow sensor and its connection on the ADIO module: plug, wires, contact corrosion, damaged cables
- The sensor's resistance (NTC 10 kΩ) at the unplugged connector, compared with the manual's curve
- The ADIO electronics module, to be replaced if needed