PlusBus voltage fault
Blocking: it retries by itself
The PlusBus voltage, the link between the boiler and its extension modules and Vitotrol 200-E remote controls, has failed. The modules on the PlusBus switch to emergency mode: the boiler is not in fault, but our technician needs to find the faulty part.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show F.100?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code F.100
The meaning depends on the boiler: find yours below.
PlusBus voltage fault
What our technician checks
- The power switch off for at least 2 minutes, then back on
- No more than 2 Vitotrol 200-E on the PlusBus
- The total PlusBus cable length: under 50 m
- The connection at plug 74 of the HMU and of all PlusBus participants
- Seating of plugs and wires, contact corrosion and cable condition
- The bus voltage: around 24 V the HMU is fine, around 0 V it needs replacing
- Reconnecting the participants one by one, every 25 s, to find the faulty one