Abnormal temperature difference in the solar circuit
Blocking: it retries by itself
On a Vitodens One Base (200-W B2HF or B2KF, 222-F B2TF, 222-W B2LF, 242-F), with a solar installation, the temperature difference between the solar collectors and the storage cylinder is outside its tolerance, for example because of air in the solar circuit, a wrongly placed sensor or a faulty pump. The boiler keeps running, but the solar system only works in a limited way and gives no solar yield: our technician needs to check it.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show F.477?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code F.477
The meaning depends on the boiler: find yours below.
Solar temperature differential
What our technician checks
- The flow in the solar circuit (too low or none) and the flow rate settings
- Air and dirt in the solar circuit
- The system pressure
- The operation of the non-return valves
- The circulation pump (operation, rated speed, dirt) and the safety temperature limiter if fitted
- The connections of sensors TS1 (hot water) and TS2 (collector) on the ADIO electronics module (EM-S1): plug, wires, contact corrosion, damaged cables
- The resistance of both sensors (TS1: NTC 10 kΩ, TS2: NTC 20 kΩ), sensors replaced if needed
- The interval function of the solar circuit pump, to be switched on if needed