No ignition spark
Breakdown: the boiler is stopped
The boiler is not making a spark to light its burner. The burner has locked out for safety and the boiler stops heating until it is reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show F.359?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code F.359
The meaning depends on the boiler: find yours below.
No ignition spark
What our technician checks
- The ignition electrode's insulation
- The 230 V supply at the igniter input during ignition
- The burner control unit (BCU), replaced if that voltage is missing
- The igniter, replaced if the voltage is present
- The igniter and ignition electrode cables