CAN bus communication fault
Breakdown: the boiler is stopped
Communication on the CAN bus, the link between the boiler's central electronic module (HMU) and the parts connected to it, has failed. The burner goes into fault: the boiler stops heating and only starts again after a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show F.160?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code F.160
The meaning depends on the boiler: find yours below.
CAN-BUS communication fault
What our technician checks
- The connecting cable between the HMU and all CAN bus participants
- Seating of plugs and wires, contact corrosion and cable condition
- Bus termination: one 120 Ω resistor on the first and the last participant
- The resistance between CAN L and CAN H with power off: about 60 Ω
- Reconnecting the participants one by one until F.160 returns
- The faulty cable or CAN bus participant, to be replaced